| Power Input | Unregulated 10 ~ 30 VDC |
| Operating Temperature | -10 ~ 70°C (14 ~ 158°F) |
| Storage Temperature | -25 ~ 85°C (-13 ~ 185°F) |
| Operating Humidity | 5 ~ 95% RH |
| Supported Protocols | ASCII command and Modbus/RTU |
| ADAM-4055 Digital I/O | 8 inputs, 8 outputs (open collector to 40V, 200mA) |
| ADAM-4055 Isolation Voltage | 2,500 VDC |
| ADAM-4056SO Digital Outputs | 12 channels, 1A per channel, Source type |
| ADAM-4056SO Isolation Voltage | 5000 VDC |
| ADAM-4080 Counter Channels | 2 independent counters (32-bit + 1-bit overflow) |
| ADAM-4080 Input Frequency | 50 kHz max. |
| ADAM-4080 Frequency Measurement Range | 5 Hz ~ 50 kHz |
| Certification | FCC, CE, UL (ADAM-4080) |
| Watchdog Timer | System (1.6 second) & Communication |